Permit Number: T20OT00584
Parcel: 11520005P

Review Status: Completed

Review Details: C OF O

Permit Number - T20OT00584
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2020 ELISA HAMBLIN ZONING REVIEW Approved
10/07/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: A previous Certificate of Occupancy was not located in our records. In order to receive a Certificate of Occupancy, a registered architect is required to provide a site plan that indicates the building location.
2. General: The registered architect is required to provide a building plan. In addition, a Code Analysis is required on this sheet, indicating the Occupancy Classification, Construction Type, Square Footage, if the building has an Automatic Sprinkler System, and the allowable Occupant Load.