Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2020 STEVE SHIELDS ZONING REVIEW Approved
06/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a Code Analysis on the drawings. Information required in this analysis would be the Occupancy Classification and Use per the 2018 International Building Code (IBC) Chapter 3; The actual and allowable building square footage per the IBC Table 506.2; The actual and allowable building height and number of stories per the IBC Tables 504.3 and 504.4; The Building Construction Type per the IBC Chapter 6; Requirements for an automatic sprinkler system per the IBC Section 903; Actual Occupant Load and calculation using the IBC Table 1004.5; Actual and allowable egress/exit calculations per the IBC Chapter 10; Actual and allowable Exit Access Travel Distance per the IBC Table 1017.2; Accessibility requirements per the IBC Chapter 11 and the 2009 ICC/ANSI. The services of a professional architect licensed in the State of Arizona might be needed for this analysis and information.
2. General: It appears from the Floor Plan this drawing received a Certificate of Occupancy in 1993. If a copy of that C of O was provided, a reduction in much of the information listed above might be warranted. Please verify.