Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20OT00056
Parcel: 11706067A

Address:
218 N 4TH AV

Review Status: Completed

Review Details: C OF O

Permit Number - T20OT00056
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2020 DJELLEN1 ZONING REVIEW Approved
01/17/2020 RMCCOY1 BUILDING-COMMERCIAL REVIEW Completed