Permit Number: T20CM09337
Parcel: 117121930

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09337
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 JPEELDA1 FIRE REVIEW Approved
01/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Clarify the capacity of the VRF condensing unit, CU-1A. There appears to be two different schedules for the unit.
01/07/2021 ROBERT SHERRY WATER REVIEW Completed
01/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/15/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/20/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/20/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/27/2021 ELISA HAMBLIN ZONING REVIEW Approved