Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM09321
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2021 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 01/14/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building. Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: Provide a site plan showing all buildings, R106.1.1. Show setbacks to property lines and location of utility lines to the building. FLOOR PLAN: Show door locations and window sizes with type identified as XO or SH. FRAMING PLAN: Provide a roof framing plan showing beam and rafter location and sizes. SECTIONS - DETAILS: Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and floor separation from grade. Show rating of insulation both walls and ceiling. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade. PLUMBING PLANS: Provide piping details showing code compliant materials and sizes or show relocated fixtures. MECHANICAL PLANS: Provide equipment details showing code compliant components, locations and sizes, or show relocated components. ELECTRICAL PLANS: Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection. INTERNATIONAL ENERGY CONSERVATION CODE: Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better. OUTDOOR LIGHTING CODE Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly). If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 01/21/2021 | ALEXANDRA HINES | ZONING | REVIEW | Reqs Change | 1. Provide dimension of North and South side setbacks on plan. Setback in R-1 zone is 6' or 2/3(H), greater dimension applies. If not complying, submit for separate Design Development Option (DDO) application. Proposed setback is unknown, so is resubmittal required showing dimension prior to DDO application. Alexandra Hines alexandra.hines@tucsonaz.gov |
| 01/21/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed |