Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T20CM09289
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2021 | ANDREW CONNOR | NPPO | REVIEW | Passed | |
| 01/04/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 01/20/2021 | NMARTEL1 | ZONING | REVIEW | Approved | |
| 01/21/2021 | PC_JEDER1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Ballast System is being used: 1. Equipment on existing roofs: It is the responsibility of the applicant submitting for permitting to verify that the roof on which the equipment is to be installed was legally permitted, is in good structural condition, and otherwise provides for a minimum residual load capacity meeting or exceeding 4 psf. 2. Uplift on panels: It is the responsibility of the applicant submitting for permitting to comply to the uplift structural calculation & submission for review and approval as part of the plan set. 3. Submit the Structural Calculations for items 1 & 2 above. This is to be done by an Arizona Structural Engineer Registrant. |