Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM09285
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T20CM09285 R2 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SECTIONS - DETAILS: 1. A gap between roof deck and insulation requires venting for moisture control. Show a calculation for determining the minimum attic ventilation opening size using 1 to 150 of attic area in compliance with R806.2 or show an unvented roof assembly with an air-impermeable rigid insulation material (minimum R-5 value) applied correctly to either side of the roof sheathing, R806.5. Show a code compliant roof design with insulation types on sheet #6. OUTDOOR LIGHTING CODE 1. Show the proposed fixture as full cut-off FCO style or provide a completed Outdoor Lighting Calculation including the unshielded lumen limit for verifying exterior lighting compliance on sheet #9. The lumen limit is 11,000 lumens per acre, therefore the plan exceeds the maximum unshielded allowance. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 04/14/2021 | JPEELDA1 | FIRE | REVIEW | Approved | Total under roof is greater than 3,600 sq. ft., this house will require a residential sprinkler system unless the fire flow in the nearest hydrant is a minimum of 2,000 GPM for 2 hours duration at 20 psi residual pressure. Contact Tucson Water engineering for a hydraulic analysis. Provide notes on plan regarding verification of fire flow and proximity of hydrant or intent to install a fire sprinkler system. If a system will be installed, residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A minimum of ¾” meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2018 IFC and NFPA 13D. |
| 04/14/2021 | JPEELDA1 | FIRE | REVIEW | Approved | Notes conflicted with plans for square footage. Plans show that they are under the 3,600 sq feet for fire sprinklers. |
| 04/23/2021 | AWARNER1 | ZONING | REVIEW | Approved | |
| 04/28/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | The Grading DP needs to be approved before the building plans can be approved. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |