Permit Number: T20CM09217
Parcel: Unknown

Address:
3778 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09217
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The permit application describes the proposed work as "Adding Tortilla Production and Sales." Provide plumbing plans for the new work, including water isometrics, waste and vent isometrics, industrial waste interceptors, etc. Reference: Section 107.2.1, IBC 2018.
2. Recalculate the number of required plumbing fixtures for the building using the occupant load based on 8,760 square feet. Item 7 of the Code Review has used a total of 44 occupants rather than 30 men and 30 women. Reference: Sections 2902.1 and 2902.2, IBC 2018.
01/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the activities that will be taking place in this suite and evaluate the exhaust and ventilation requirements. Reference: Sections 401.2 and 401.3.1, IMC 2018.
2. Any commercial cooking appliance will require the installation of an appropriate exhaust hood. Reference: Section 507.1, IMC 2018.
01/27/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/27/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
02/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
02/10/2021 JPEELDA1 FIRE REVIEW Approved
02/10/2021 STEVE SHIELDS ZONING REVIEW Approved
02/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Project Notes: The Project Notes indicate the previous tenant as Design Professional Services, Retail, Office, and Factory uses. There is a project note in Permits Plus that indicates this was Restaurant Services and Sales previously. Please verify if this is a change of use.
2. Sheet A1; Code Review (Bathroom Requirements): Using the B Occupancy Classification, 30 males and 29 females, the IBC Table 2902.1 requires 1/25 for the first 50 of each sex. This would require two waterclosets per sex. Please verify. This may require an appeal from the Building Official.
3. Sheet A3; Floor Plan: The Retail Area (461 SF) indicates an occupant load of 8 using 150 SF/occupant (461/150 = 4 occupants). Revise the occupant load for Retail use per the IBC Table 1004.5 (60 SF/occupant).
4. Sheet A3; Floor Plan: Please indicate the actual Exit Access Travel Distance on the plan for each exit. Verify the requirements of the IBC Section 1017 and Table 1017.2 are met.
5. General: Please provide written responses to all review comments.
02/16/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed