Permit Number: T20CM09213
Parcel: 11706168A

Address:
33 S 5TH AV #205

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09213
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/06/2021 JPEELDA1 FIRE REVIEW Approved
01/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/14/2021 ROBERT SHERRY WATER REVIEW Completed
01/19/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The penetration of the fire barrier enclosing the stairwell by the relocated ductwork and air devices for the purpose of ventilating the office area is not allowed. Reference: Section 607.5.2, IMC 2018 and Sections 1023.5 and 1024.6, IBC 2018.
01/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
01/25/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/25/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/03/2021 NMARTEL1 ZONING REVIEW Approved