Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM09213
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 01/06/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 01/14/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/14/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/19/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The penetration of the fire barrier enclosing the stairwell by the relocated ductwork and air devices for the purpose of ventilating the office area is not allowed. Reference: Section 607.5.2, IMC 2018 and Sections 1023.5 and 1024.6, IBC 2018. |
| 01/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 01/25/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/25/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2021 | NMARTEL1 | ZONING | REVIEW | Approved |