Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM09166
Parcel: 126210890

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM09166
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2021 ANDREW CONNOR NPPO REVIEW Passed
01/27/2021 SBLOOD1 ENGINEERING REVIEW Passed
01/27/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show each pipe segment sized in conformance with Table G2413.4(1). Show a 1-1/4" pipe between the meter and branch off tee for the new water heater and furnace. This segment supplys 260,000 BTUs at a developed length of 72'.

Show any additions or alterations to the mechanical systems.
01/29/2021 SAMUEL ROGERS ZONING_HISTORIC REVIEW Passed
01/29/2021 SAMUEL ROGERS ZONING REVIEW Approved
02/08/2021 JPEELDA1 FIRE REVIEW Reqs Change Your plans shall show the referenced code IFC, IBC and IRC.
Your plans shall also show the existing square footage and the new square footage that you are adding.