The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM09144
Parcel: 13423411A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09144
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/05/2021 SBLOOD1 ENGINEERING REVIEW Passed
01/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/05/2021 JPEELDA1 FIRE REVIEW Approved
01/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G4; Code Data (Exits): The corridor dead end distance indicates 20'-0" per the IBC Section 1018.4. Please revise the reference and the allowable distance per the 2018 IBC.
2. Sheet G4; Code Data (Accessibility/Employee Work Areas): The current edition of the ICC/ANSI used by the City of Tucson is the 2009. Please revise the reference to Table 1109.12.2 in Accessibility and the reference to the 2019 ICC/ANSI in Employee Work Areas.
3. Sheet A1; Partition Types: Partition Types C, D, and E indicate a reference to an anchor Detail 4/A1 at the partition base. Please revise that reference.
4. General: Please provide written responses to all review comments.
01/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/07/2021 ROBERT SHERRY WATER REVIEW Completed
01/19/2021 NMARTEL1 ZONING REVIEW Approved