Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM09144
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/05/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 01/05/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/05/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 01/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G4; Code Data (Exits): The corridor dead end distance indicates 20'-0" per the IBC Section 1018.4. Please revise the reference and the allowable distance per the 2018 IBC. 2. Sheet G4; Code Data (Accessibility/Employee Work Areas): The current edition of the ICC/ANSI used by the City of Tucson is the 2009. Please revise the reference to Table 1109.12.2 in Accessibility and the reference to the 2019 ICC/ANSI in Employee Work Areas. 3. Sheet A1; Partition Types: Partition Types C, D, and E indicate a reference to an anchor Detail 4/A1 at the partition base. Please revise that reference. 4. General: Please provide written responses to all review comments. |
| 01/07/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/07/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/19/2021 | NMARTEL1 | ZONING | REVIEW | Approved |