Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Designate a branch circuit and panel.
2. Verify wiring methods, conduit, conductor sizes and types, total additional load and total load on the branch circuit if utilizing existing branch circuit.
3. Rating of OCPD.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.