Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM09123
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The previous plan review comments were not completely addressed. The note at the bottom of the Amazon plan states that a dedicated branch circuit is required for this equipment and the additional notes included on the second page (non Amazon) gives the option to share power for the proposed installation with an existing branch circuit. This contradicts Amazons instructions. NEC art 110.3B requires products to be installed per the manufactures instructions. Please revisit the previous review comments and revise the plans accordingly. Ref 2018 IBC sec 107.2.1, 2017 NEC. |