Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM09123
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Designate a branch circuit and panel. 2. Verify wiring methods, conduit, conductor sizes and types, total additional load and total load on the branch circuit if utilizing existing branch circuit. 3. Rating of OCPD. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |