Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM09121
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/14/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Third comment: Comment not resolved. The Sanitary & Vent Riser Diagram on P1.1 still shows the fixture drain of the automatic washing machine discharging to a 2" horizontal drain.] [Second comment: The plumbing plan has been corrected but not the isometric on P1.1 which still shows a 2" horizontal drain.] [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/14/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |