Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM09121
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM09121
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. The Sanitary & Vent Riser Diagram on P1.1 still the fixture drain of the automatic washing machine discharging to a 2" horizontal drain. [Second comment: The plumbing plan has been corrected but not the isometric on P1.1 which still shows a 2" horizontal drain.] [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.]