Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The Sanitary & Vent Riser Diagram on P1.1 still the fixture drain of the automatic washing machine discharging to a 2" horizontal drain. [Second comment: The plumbing plan has been corrected but not the isometric on P1.1 which still shows a 2" horizontal drain.] [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.] |