Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM09121
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/12/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/12/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The plumbing plan has been corrected but not the isometric on P1.1 which still shows a 2" horizontal drain. [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.] |
10/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |