Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM09121
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM09121
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1, E2. Plans show a new SES (N) and new panel '3P'. Please provide a complete electrical line diagram including grounding, load calculations, AIC ratings.
2. Provide complete panel schedules.
3. Indicate if the Fan coils are existing or new. Also verify that there is a switched lighting outlet in the ceiling cavity for the fan units as required per NEC 210.70A(3).
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2021 PCAMARE1 OUT TO CUSTOMER Completed