Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E1, E2. Plans show a new SES (N) and new panel '3P'. Please provide a complete electrical line diagram including grounding, load calculations, AIC ratings. 2. Provide complete panel schedules. 3. Indicate if the Fan coils are existing or new. Also verify that there is a switched lighting outlet in the ceiling cavity for the fan units as required per NEC 210.70A(3). Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |