Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T20CM09119
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide plans sealed by an Electrical Engineer registered in the State of Arizona. Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide a complete line diagram include load calculations, Grounding detail. 3. Show all feeder conduit, conductor sizes and types, Including OCPD ratings, Available fault current and AIC ratings of the Electrical service and downstream equipment. 4. Provide complete panel schedules. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |