Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide plans sealed by an Electrical Engineer registered in the State of Arizona.
Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a complete line diagram include load calculations, Grounding detail.
3. Show all feeder conduit, conductor sizes and types, Including OCPD ratings, Available fault current and AIC ratings of the Electrical service and downstream equipment.
4. Provide complete panel schedules.

Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.