Permit Number: T20CM09118
Parcel: 117145120

Address:
499 S MEYER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM09118
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change NEW EXTERIOR LIGHTING REQUIRES COMPLIANCE
with City of Tucson Outdoor Lighting Code; the total property lighting limit for area E3 is 55,000 lumens per acre and the unshielded limit for area E3 is 11,000 lumens per acre. Include all exterior fixtures on the property in the calculations. Separately show the fixture wattage both full cut-off and unshielded styles for determining exterior lighting limits. CONSIDER FULL CUT-OFF STYLE FIXTURES.

SHOW A LIGHTING CIRCUIT FOR NEW ELECTRICAL WIRING ON A PLAN.
04/12/2021 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl the building plans are approved by Historic Zoning cannot approve the plans.
05/13/2021 JBROWN2 ZONING_HISTORIC REVIEW Approved