Permit Number: T20CM09098
Parcel: 12910112A

Address:
1406 S CURTIS AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM09098
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 ANDREW CONNOR NPPO REVIEW Passed
01/07/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Each building requires a unique street address. Provide a site plan showing a separate address on each dwelling perhaps A & B along with 1106 on one building. The other duplex building requires a different permit.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

Each dwelling unit providing complete independent living facilities requires compliance with design ordinances for handicap, solar water, photo-voltaic and gray water preparations. Design Ordinances adopted by the City of Tucson.

Individual dwelling units in duplexes must be separated by 1-hour fire-resistance rated assemblies from floor to bottom of roof sheathing, R302.3. Update keynote #10/A5.

Show an individual accessible water supply shut off for each dwelling unit (exterior), P2903.9.1.

Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans.

Update note #33/A8 to 90% rather than 75%, N1104.1.
01/14/2021 NICHOLAS ROSS ZONING REVIEW Reqs Change Please correct site plan to show only the parcel related to Permit Number T20CM09098.

A proposal that requires five or more parking spaces must comply with commercial requirements (paving, striping, curbs etc.)

Additionally provide setback information and building heights to verify setback requirements.
12/30/2020 SBLOOD1 ENGINEERING REVIEW Passed