Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM09091
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T20CM09091 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: A new dwelling unit (includes a kitchen) requires collection of development impact fee when the building permit is processed, City of Tucson Ordinance #11203. Each dwelling unit building requires a separate street address, R319 GENERAL COMMENTS: 1. A dwelling unit providing complete independent living facilities requires compliance with design ordinances for handicap, solar water, photo-voltaic and gray water preparations. Design Ordinances adopted by the City of Tucson. SITE PLAN: 1. Clarify the location of existing and proposed electric lines from property line to building, R106.1.1. SECTIONS - DETAILS: 1. Show a cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface (R403.1) with 12” minimum width for wood framed walls R403.1.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt with length providing 7” embedment into concrete foundation, R403.1.66. ELECTRICAL PLANS: 1. TEP usually requires the service panel on the property at the closest building to the service transformer. 2. Provide a panelboard clear working space of 30”wide x 36”deep, E3405.2. 3. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6. Please contact the plans reviewer if you have any questions: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 06/08/2021 | NICHOLAS ROSS | ZONING | REVIEW | Reqs Change | Parcel does not have enough sqft to have a second kitchen on site. Remove the proposed oven and full size refrigerator and it would be conidered a "Sleeping Quarters." |