Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T20CM09085
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/29/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/18/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1.The 3rd submittal did not include the full set of updated electrical plans. Only the (already) approved electrical line diagram and site plan. The 2018 IECC Energy calculations Comchecks and 4 panel schedules were also included but not approved yet. 2.The submittal needs to include the updated site lighting plan along with full compliance with the 2012 Tucson/Pima County Outdoor Lighting on the plan. This was requested in previous electrical reviews for this project but not addressed. 3.The submittal also did not include an electrical power floor plan. 4.Please include a complete set of up to date electrical plans in the next submittal. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements |
| 05/27/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved |