Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T20CM09077
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/14/2021 | PETER MCLAUGHLIN | ZONING | REVIEW | Passed | |
| 01/14/2021 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
| 01/25/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 02/05/2021 | LBOWERS1 | COMMUNICATIONS | REVIEW | Needs Review | |
| 12/29/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete electrical plans including all electrical equipment, Line diagram, Feeders, Conduit conductor sizes and types, Exterior lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2021 | LBOWERS1 | OUT TO CUSTOMER | Passed |