Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM09076
Parcel: 14117690C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09076
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/04/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
01/04/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/04/2021 ROBERT SHERRY WATER REVIEW Completed
01/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/04/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/05/2021 SBLOOD1 ENGINEERING REVIEW Passed
01/05/2021 JPEELDA1 FIRE REVIEW Approved
01/11/2021 NICHOLAS ROSS ZONING REVIEW Approved