Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM09076
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/04/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
01/04/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/04/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/04/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/05/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
01/05/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
01/11/2021 | NICHOLAS ROSS | ZONING | REVIEW | Approved |