Permit Number: T20CM09056
Parcel: 136361230

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM09056
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2021 LBOWERS1 NPPO REVIEW Needs Review
01/15/2021 LBOWERS1 ENGINEERING REVIEW Needs Review
01/15/2021 LBOWERS1 BUILDING-RESIDENTIAL REVIEW Needs Review
02/11/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T20CM09056
7881 E Nicaragua Dr
Attached Garage and Porch Conversation to Familyroom

TRANSMITTAL: February 11, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of less than 9’-0” the required perimeter yard setback from the proposed garage to the east property line is 6’-0”, proposed setback is 3’-0”.

The following comments will need to be addressed prior to resubmittal:

1. The “EXSITING RAMADA” called out under Site Plan Keynote 5 shows up on the site sometime after 2016 based on aerial photos. There are no permits for this ramada on file and it will need to be included in this permit.

2. There is some type of porch structure attached to the northwest side of the house. This structure shows up sometime after 2018 based on aerial photos. There are no permits for this porch structure on file and it will need to be included in this permit.

3. There is a what appears to be some type of shed along the west side of the existing dwelling, show this shed on the plan and include it in the lot coverage calculation.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin @tucsonaz.gov or (520) 837-4966