Permit Number: T20CM09036
Parcel: 12406151B

Address:
187 N PARK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09036
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/05/2021 JPEELDA1 FIRE REVIEW Approved
01/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/07/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
01/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the connected natural gas loads or input ratings for each appliance and coordinate the natural gas loads for the rooftop units with the mechanical plans. Revise the natural gas pipe sizes as required.
2. Appliances (e.g. beverage dispensers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
01/07/2021 ROBERT SHERRY WATER REVIEW Completed
01/07/2021 NMARTEL1 ZONING REVIEW Approved
01/15/2021 DTRAMME1 ENGINEERING REVIEW Passed
12/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved