Permit Number: T20CM09029
Parcel: 12708017A

Address:
5450 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM09029
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the exhaust inlets for the manicure and pedicure stations. The inlets cannot just be “above” the areas but must be within 12-inches horizontally and 12-inches vertically of the point of polish application. [Second comment: Both manicure stations and pedicure chairs require 50 CFM exhaust inlets located within 12-inches horizontally and 12-inches vertically of the point of polish application.] [initial comment: A barber shop requires 0.5 CFM of exhaust per square foot while both the beauty salon and nail salon require 0.6 CFM of exhaust per square foot. In addition, each manicure and pedicure station requires 50 CFM of source capture exhaust. Reference: Table 403.3.1.1 (see also footnote h), and Section 502.20, IMC 2018.]
2. Clarify the equipment tags for the exhaust fans and coordinate the air balance schedule. The exhaust fan for the barber shop is listed as both EF-3 and EF-4. The beauty salon requires 924 CFM of exhaust but only EF-2, with 500 CFM, is shown in the beauty parlor. EF-3 is shown in the nail salon, with 300 CFM, but it is not shown that way in the air balance schedule.
07/20/2021 ROBERT SHERRY WATER REVIEW Completed
07/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed