Permit Number: T20CM09029
Parcel: 12708017A

Address:
5450 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM09029
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a specification for the pedicure chairs (i.e. if there is there a spray attachment, a reduced pressure backflow preventer will be required for each water connection). [Initial comment: See https://www.tucsonaz.gov/files/pdsd/codes-ordinances/FootSpa_Plumbing.pdf for installation requirements for pedicure chairs (aka foot spas).]
07/06/2021 ROBERT SHERRY WATER REVIEW Reqs Change The water service pipe from the meter will need to be increased to 1-1/4-inches to keep the water velocity below 8 FPS; the water service pipe is shown as 1-ich on the drawing. The RP is noted as 1-inch on the drawing but as 1-1/4-inches on the water calculations. [Second comment: The corrected water demand of 26 GPM will require the 1-inch water service pipe to be increased to 1-1/4-inch to keep the water velocity below 8 FPS. Reference: Section 303.2, IPC 2018.] [Initial comment: Show that the proposed plumbing work will not cause the existing water supply system to become overloaded. Reference: Section 107.2.1, IBC 2018.]
07/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Both manicure stations and pedicure chairs require 50 CFM exhaust inlets located within 12-inches horizontally and 12-inches vertically of the point of polish application. [initial comment: A barber shop requires 0.5 CFM of exhaust per square foot while both the beauty salon and nail salon require 0.6 CFM of exhaust per square foot. In addition, each manicure and pedicure station requires 50 CFM of source capture exhaust. Reference: Table 403.3.1.1 (see also footnote h), and Section 502.20, IMC 2018.]