Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T20CM09029
Parcel: 12708017A

Address:
5450 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM09029
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Gemera; The previous comments were not addressed. A code analysis on the drawings is required to indicate the Occupancy Classification, Occupant Load, Construction Type, Tenant Space Square Footage, Exiting requirements, Accessibility, and Plumbing Fixture requirements.

Previous Comments:
1. General: In order to review a project, the minimum requirements for submittal documents must follow the IBC Section 107. Since this permit is for a change of use, the documents to be submitted must be prepared by a registered design professional. Please retain the services of such a person so that the project review and approval may proceed.
2. General: It might be helpful to review the permit application procedure and requirements at the City of Tucson website www.tucsonaz.gov/PDSD.
02/18/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a mechanical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018.
2. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the provisions of the applicable codes. Reference: Section 107.2.1, IBC 2018.
02/18/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a plumbing design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018.
2. Provide sufficient information to show the extent of the proposed plumbing modifications and show that the installation of the new plumbing fixtures will comply with the provisions of the applicable codes. Reference: Section 107.2.1, IBC 2018.
02/18/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/18/2021 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
2. Show that the proposed plumbing work will not cause the existing water supply system to become overloaded. Reference: Section 107.2.1, IBC 2018.
03/01/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show codes being applied to the TI
Plans shall show if the building has fire sprinklers
If you have any questions please contact me:
Jennifer.Peel-Davis@Tucsonaz.gov
03/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change There is not a new submitted set that addresses the comments from the first review.
03/04/2021 STEVE SHIELDS ZONING REVIEW Approved
03/04/2021 SSHIELD1 ZONING HC REVIEW Passed