Permit Number: T20CM09029
Parcel: 12708017A

Address:
5450 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM09029
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
01/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
01/11/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
01/12/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM09029
January 12, 2020

Please follow the instructions on the city of Tucson permit application page. If the applicant is proposing an interior remodel of a new business, follow the link below under "Building Permits"
https://www.tucsonaz.gov/pdsd/apply-permit

If you have any questions about this transmittal, please email me at Nicholas.Martell@tucsonaz.gov
01/15/2021 DTRAMME1 ENGINEERING REVIEW Passed
12/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete electrical plans sealed by an Engineer registered in the State of Arizona, including all electrical fans, lighting.
2. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
3. See Building review comments.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.
12/29/2020 JPEELDA1 FIRE REVIEW Reqs Change Plans are required for review
12/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: In order to review a project, the minimum requirements for submittal documents must follow the IBC Section 107. Since this permit is for a change of use, the documents to be submitted must be prepared by a registered design professional. Please retain the services of such a person so that the project review and approval may proceed.
2. General: It might be helpful to review the permit application procedure and requirements at the City of Tucson website www.tucsonaz.gov/PDSD.
12/29/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review