| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/27/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the gas elevation detail (A/P1.0) with the gas diagram (B/P1.0) and with the plumbing floor plan, 1/P1.0. In any case, some of the existing 2" pipe will need to be replaced with 2-1/2" pipe (e. g. 1054 CFH @ 200'). [Initial comment: Provide a complete diagram of the natural gas distribution system showing the all of the existing and proposed loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.] |
| 02/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2021 | LBOWERS1 | OUT TO CUSTOMER | Passed |