Permit Number: T20CM08961
Parcel: 125111560

Address:
3701 E 3RD ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM08961
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the gas elevation detail (A/P1.0) with the gas diagram (B/P1.0) and with the plumbing floor plan, 1/P1.0. In any case, some of the existing 2" pipe will need to be replaced with 2-1/2" pipe (e. g. 1054 CFH @ 200'). [Initial comment: Provide a complete diagram of the natural gas distribution system showing the all of the existing and proposed loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.]
02/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2021 LBOWERS1 OUT TO CUSTOMER Passed