Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide the specifications and listing information for the proposed water heaters. Reference: Sections 303.2 and 501.5, IPC 2018 and Section 107.2.1, IBC 2018.
3. Provide a complete diagram of the natural gas distribution system showing the all of the existing and proposed loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.
4. Show how the proposed water heaters will be installed in accordance with their listing. Reference: Section 303.1, IFGC 2018.