Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM08941
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/19/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per the application for permit, the applicant describes the Electrical scope of work as upgrading the Electrical and switchgear. The panel schedules show specific Electrical equipment with loads connected. Provide complete Electrical floor plans with the Electrical equipment and designated feeders and branch circuits designated to correlating panels. Please show in detail what is the proposed new work and what is existing, including panels and all Electrical equipment. 2. Show the locations of all the panelboards on the premises. 3. Ref; Plan Sheet E-101. 'DEMOLITION NOTES', refer to plan sheet AD-101 to verify extent of the demolition, all electrical work in nature etc. The Electrical Plan Reviewer could not locate this plan in the plan set. Please clarify. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/20/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |