Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM08908
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the "Preliminary, not for Construction" label from the drawings.). Reference: Section 107.2.1, IBC 2018. 3. Specify the size of the openings in the screen protecting the air intake opening. Reference: Section 401.5, IMC 2018. 4. Relocate the exhaust fan termination to a point 10-feet above grade. Reference: Section 501.3.1 (2), IMC 2018. |
| 01/19/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide plans sealed by an Engineer or Architect Registered in the State of Arizona. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/20/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |