Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM08851
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2021 | LSHAMIS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 01/25/2021 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | See comments on drawings sent by separate email. - In plumbing drawings Provide gas plan / gas isometric with gas appliance schedule, total gas demand, longest length to furthest appliance, pipe sizes and materials, etc. as required to have a complete gas piping design. - Provide Plumbing Site Plan (or Civil Utility Plan whichever is appropriate) - Apply and pay for separate sewer permit. Provide Sewer Receipt # on Architectural Site Plan and Plumbing Site Plan (or Civil Utility Plan as appropriate). |
| 01/25/2021 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | See comments on drawings sent by separate email. - The rated color temperature of light sources (lamps and fixtures) shall not exceed 3500K. |
| 01/25/2021 | PIMA COUNTY | WATER | REVIEW | Reqs Change | - Provide copy of water plan showing public water line being connected to, service meter location and backflow prevention device location. Show water service line to building, including pipe size and mater and S.O.V. |
| 01/25/2021 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | See comments on drawings sent by separate email. - Provide an architectural site plan that includes utility information such as incoming water service, water meter location and size, building sewer connection to the public sewer, sewer fee receipt #, upstream manhole elevation in reference to FFE. Gas meter location, grease trap location. Etc. |
| 01/25/2021 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | See comments on drawings sent by separate email. - Provide Condensing Unit schedule. |
| 01/26/2021 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T20CM08851 McDonalds - 1st Review 4555 S Campbell Av TRANSMITTAL DATE: 01/26/2021 DUE DATE: 01/13/2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: This building plan will not be able to be approved until DP20-0081 is issued. Additional comments on this building permit may be applicable once DP20-0081 is issued. If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 02/05/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1 DEVELOPMENT PACKAGE MUST BE APPROVED FIRST. 2 BUILDING DRAINAGE MUST MATCH DP. DO NOT DIRECT PRIMARY RAIN LEADERS TO SIDEWALKS. |
| 12/30/2020 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/08/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |