Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/25/2021 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change See comments on drawings sent by separate email.
- In plumbing drawings Provide gas plan / gas isometric with gas appliance schedule, total gas demand, longest length to furthest appliance, pipe sizes and materials, etc. as required to have a complete gas piping design.
- Provide Plumbing Site Plan (or Civil Utility Plan whichever is appropriate)
- Apply and pay for separate sewer permit. Provide Sewer Receipt # on Architectural Site Plan and Plumbing Site Plan (or Civil Utility Plan as appropriate).
01/25/2021 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change See comments on drawings sent by separate email.
- The rated color temperature of light sources (lamps and fixtures) shall not exceed 3500K.
01/25/2021 PIMA COUNTY WATER REVIEW Reqs Change - Provide copy of water plan showing public water line being connected to, service meter location and backflow prevention device location. Show water service line to building, including pipe size and mater and S.O.V.
01/25/2021 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change See comments on drawings sent by separate email.
- Provide an architectural site plan that includes utility information such as incoming water service, water meter location and size, building sewer connection to the public sewer, sewer fee receipt #, upstream manhole elevation in reference to FFE. Gas meter location, grease trap location. Etc.
01/25/2021 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change See comments on drawings sent by separate email.
- Provide Condensing Unit schedule.
01/26/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T20CM08851
McDonalds - 1st Review
4555 S Campbell Av

TRANSMITTAL DATE: 01/26/2021

DUE DATE: 01/13/2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: This building plan will not be able to be approved until DP20-0081 is issued. Additional comments on this building permit may be applicable once DP20-0081 is issued.


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
02/05/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1 DEVELOPMENT PACKAGE MUST BE APPROVED FIRST.
2 BUILDING DRAINAGE MUST MATCH DP. DO NOT DIRECT PRIMARY RAIN LEADERS TO SIDEWALKS.
12/30/2020 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2021 PCAMARE1 OUT TO CUSTOMER Completed