Permit Number: T20CM08839
Parcel: 113074130

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM08839
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise Detail 201 to show the temperature sensor for the Aquastat upstream of the recirculation pump and cause the pump to shut down when the temperature is 110 degrees Fahrenheit or greater. Reference: Section 303.2, IPC 2018.
2. Revise Detail 201 to show shut off valves for maintenance of the recirculation pump and prior to the check valve in the CW supply to the water heater. Reference: Section 606.2, IPC 2018.
3. Clarify the configuration of the waste and vent piping for the new shower and breakroom sink (i.e. provide a riser diagram). Reference: Section 901.2.1, IPC 2018.
01/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/11/2021 ROBERT SHERRY WATER REVIEW Completed
01/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/20/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/20/2021 DAN SANTA CRUZ BUILDING-COMMERCIAL REVIEW Approved
01/26/2021 SROGERS2 ENGINEERING REVIEW Passed
01/26/2021 SAMUEL ROGERS ZONING REVIEW Approved
12/30/2020 JPEELDA1 FIRE REVIEW Approved