Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM08839
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise Detail 201 to show the temperature sensor for the Aquastat upstream of the recirculation pump and cause the pump to shut down when the temperature is 110 degrees Fahrenheit or greater. Reference: Section 303.2, IPC 2018. 2. Revise Detail 201 to show shut off valves for maintenance of the recirculation pump and prior to the check valve in the CW supply to the water heater. Reference: Section 606.2, IPC 2018. 3. Clarify the configuration of the waste and vent piping for the new shower and breakroom sink (i.e. provide a riser diagram). Reference: Section 901.2.1, IPC 2018. |
01/11/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/11/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/13/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/20/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/20/2021 | DAN SANTA CRUZ | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/26/2021 | SROGERS2 | ENGINEERING | REVIEW | Passed | |
01/26/2021 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
12/30/2020 | JPEELDA1 | FIRE | REVIEW | Approved |