Permit Number: T20CM08824
Parcel: 123060010

Address:
1946 E ELM ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08824
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 ANDREW CONNOR NPPO REVIEW Passed
01/14/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building.

Place each plan sheet into a single PDF file for reviewing as a complete plan set.

Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing all utilities to the building, R106.1.1. .

FLOOR PLAN:

Provide a floor plan showing each room with labeled function. Show door locations and window sizes with type identified as XO or SH.

FRAMING PLAN:

Provide a roof framing plan showing beam and rafter location and sizes.

SECTIONS - DETAILS:

Show attic venting.

Provide structural details showing code compliant materials and fasteners (include rebar) from the foundation to the roof covering of new exterior walls.
Include the foundation dimensions and floor separation from grade. Framed walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade.

PLUMBING PLANS:

Provide piping details showing code compliant materials and sizes or show relocated fixtures. Show a minimum 1” yard pipe size supplying the building for the increased water demand.

MECHANICAL PLANS:

Provide dryer venting.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit number and size. The bathroom requires a 20A receptacle. Receptacles, lighting and smoke detector circuits require arc-fault protection.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
01/21/2021 SBLOOD1 ENGINEERING REVIEW Passed
01/28/2021 NICHOLAS ROSS ZONING REVIEW Approved