Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM08683
Parcel: 117200270

Address:
180 S CHURCH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM08683
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/09/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change UNTIL DP20-0253 IS APPROVED ZONING CANNOT APPROVE THE BUILDING PLANS
02/18/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.
Provide lighting plans with the following information on the plans;
Provide a complete luminaire schedule.
Size of the parcel in acres.
See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
(d) 402.1 (light source color temperature requirements), shielding requirements, etc .
(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
(g) Specify any exceptions used.
(h) Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2021 PCAMARE1 OUT TO CUSTOMER Completed