Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T20CM08683
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/09/2021 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | UNTIL DP20-0253 IS APPROVED ZONING CANNOT APPROVE THE BUILDING PLANS |
| 02/18/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. Provide lighting plans with the following information on the plans; Provide a complete luminaire schedule. Size of the parcel in acres. See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. (d) 402.1 (light source color temperature requirements), shielding requirements, etc . (e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. (f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. (g) Specify any exceptions used. (h) Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |