Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08669
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2020 ANDREW CONNOR NPPO REVIEW Passed
12/14/2020 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM08669
Residential Addition
December 14, 2020

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. Please submit documentation that the lot split that has occurred on the property was approved by the city. Zoning review cannot find any record of a city approved split; and the lot, as is, does not meet minimum lot size standards.


If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
12/16/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM08669
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of the water line from property line (meter) to building, R106.1.1. Show an existing or upgraded 1” line to the water heater. Minimum size for a two bathroom building is usually 1”, P2903.7.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1. The 4x8 beam is undersized for required live and dead loading.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Both standard and high density batt insulation requires a space greater than provided with 2” x 6” framing, N1102.1. Identify the products that provide the intended minimum R-30 total value with a 2-layer system.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
12/21/2020 SBLOOD1 ENGINEERING REVIEW Passed