Permit Number: T20CM08649
Parcel: 132191570

Address:
2130 E AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM08649
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The reviewer could not locate the lumen calculations as requested per previous comment #2e. Plan sheet MEP 100 did not have the calculations on it as stated.

Please revise the plan to show the information requested to verift compliance with the lumen cap.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements