Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM08649
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/24/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/25/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/25/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The tankless water heater schedule shows 199 CFH for each water heater but the plumbing fixture schedule and the gas isometric show 150 MBH. [Initial comment: Coordinate the water heater schedules, gas inputs, and tag names. On sheet P002 the water heaters are called out as GWH-1 and TWH-1, 199 CFH and 150 MBH. Reference: Section 107.2.1, IBC 2018.] 2. Comment not resolved: the shut off valve is to be upstream of the dirt leg. [Initial comment: Revise the configuration of the natural gas sediment trap, as shown in the gas connection detail on sheet P400, to comply with the requirements of Section 408.4, IFGC 2018.] 3. Comment not resolved: the plumbing fixture schedule still calls for HS-1 to have an indirect waste connection with an air gap. [Initial comment: Provide a direct connection to the building drainage system for all plumbing fixtures except as allowed by Chapter 8, IPC 2018 (e.g. hand sink, HS-1). Reference: Section 301.3, IPC 2018.] 4. Comment not addressed. [Initial comment: Provide location and sizing information for gutters and downspouts. Reference: Sections 1106.1 and 1106.6, IPC 2018.] |
| 04/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Per the previous electrical plan review comments, the following items were not addressed or addressed incorrectly. Show all information on the lighting plan. The exterior luminaires marked ‘AA’ and ‘AA1’ exceed the maximum light source color of 3500K. See the ‘Luminaire Schedule’ description Design Basics. This also does not correlate with the “Lighting Compliance Notes” on plan sheet EP100, Item #2. Comment #2(c). Indicate the Lighting Area and Option used in the lumen calculations. Indicate which luminaires are Fully Shielded and Unshielded show total lumen calculations for each. Per section 104.2.1. Provide total lumen calculations for existing and propose Shielded and Unshielded luminaires compared to allowed lumens per acre. Verify compliance with the lumen caps per table 401.1 on the lighting plan as required per the OLC. Section 104.2.1. Ref; 2017 NEC, 2018 IBC sec 107.2.1, 2012 Tucson/Pima County Outdoor Lighting Code. (OLC). |
| 04/12/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/15/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |