Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM08635
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/24/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/30/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | A dishwasher may not discharge through a hydromechanical grease interceptor but it is required to discharge through a gravity grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. |
07/01/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the natural ventilation calculations. The exterior door in Seating 2 is to be closed at all times so it cannot be used for natural ventilation. Are any of the existing windows operable? If not, Seating 1 requires only 4% operable opening area but rooms Seating 2 and Seating 3 are adjoining spaces and their ventilation requirements are 8% of the total floor area. Reference: Section 402.3, IMC 2018. |
07/13/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/13/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |