Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change A dishwasher may not discharge through a hydromechanical grease interceptor but it is required to discharge through a gravity grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
07/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the natural ventilation calculations. The exterior door in Seating 2 is to be closed at all times so it cannot be used for natural ventilation. Are any of the existing windows operable? If not, Seating 1 requires only 4% operable opening area but rooms Seating 2 and Seating 3 are adjoining spaces and their ventilation requirements are 8% of the total floor area. Reference: Section 402.3, IMC 2018.
07/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2021 NGARCIA3 OUT TO CUSTOMER Completed