Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM08635
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/12/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/12/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/12/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T1.0; Building Occupancy: Although the IBC Section 303.1.1 allows Assembly Groups with less than 50 occupants to be classified as a Group B Group, the IBC Table 1004.5 determines the Occupant Load Factor based on the function of the space (in this case a Restaurant A-2). Rather than using the Occupant Load Factor of 15 SF/occupant, you can use the number of seats indicated on the floor plan. You may not use the 150 SF/occupant for a Group B Occupancy. Please verify. 2. Sheet T1.0; Plumbing Fixture Calculations: Please verify the occupant load is 15 or less to meet the requirement of a single restroom. Since there is not a change of use, but appears to be an increase in occupant load, a discussion with the Building Official would be warranted. You can contact him at Clayton.Trevillyan@tucsonaz.gov. 3. Sheet A1.0; Wall Schedule (Walls 1, 2, and 3): Please indicate the metal wall stud gauges. 4. Sheet A1.0; Floor Plan: The Occupant Load from Sheet T1.0 indicates 9. The Floor Plan indicates 5 seats in the Service Area, 2 seats in Seating 1 Area, 4 seats in Seating 2 Area, and an unspecified number of occupants on the benches in Seating 3 Area. Please confirm and/or revise the occupant load for this building. 5. General: Please provide a valuation for this projecct. 6. General: Please provide written responses to all review comments. |
01/15/2021 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
12/10/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
12/21/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations to show that the 50-gallon water heater will be safely supported from the building structure (i.e. will the wall support the water heater and shelf-). Reference: Section 301.2, IPC 2018. |
12/21/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
12/21/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/30/2020 | JPEELDA1 | FIRE | REVIEW | Approved |